Grounding and bonding are the quiet half of a safe PV system — the paths that carry fault current and keep metal from becoming energized. NEC Article 250 sets the general rules and Article 690 Part V adds the PV specifics. Here is what each conductor does and how it is sized.

Bonding vs grounding

The terms get used loosely, but they are different jobs:

The equipment grounding conductor (EGC)

The EGC bonds each piece of equipment back toward the source. For PV circuits:

See the equipment grounding conductor 250.122 reference for the sizing table.

Array bonding

Module frames and rails must be bonded into a continuous path:

The grounding electrode conductor (GEC)

The GEC connects the system grounding point to the grounding electrode:

ConductorJobSized by
EGCBonds equipment to sourceNEC 250.122 (OCPD rating)
Bonding jumpersTies array metal togetherListed hardware / mfr
GECConnects system to earthNEC 250.66 / 250.166

Common field mistakes

Grounding is where clean-looking installs quietly fail inspection. Watch for:

What a reviewer checks

On the one-line, the reviewer looks for the EGC in every circuit, the bonding method for the array, the GEC to the electrode, and that any added electrode is bonded to the existing system. Missing or unsized grounding conductors are a common correction.

Hook: grade your solar design free - same NEC checks a reviewer runs.

Grounding details vary by racking listing and AHJ, so follow your equipment's instructions and confirm local requirements. A licensed electrician or PE must review and stamp the final design. To see how grounding fits the whole package, read what is in a solar permit set or browse the reference library.

FAQ

What is the difference between grounding and bonding?

Bonding ties metal parts together so they share a potential; grounding connects that bonded system to earth through a grounding electrode.

How is the equipment grounding conductor sized for PV?

The EGC is sized from NEC 250.122 based on the circuit overcurrent device rating, with PV-specific rules in 690.45.

Do I need a separate ground rod for solar?

Usually the PV system bonds to the existing grounding electrode system; an additional electrode may be required by some AHJs but must be bonded to the existing one.

Related: Design & sizing

Educational reference, reviewed 2026-07. A design aid, not a substitute for a licensed electrician or PE. Confirm the enforced NEC edition and local amendments with your AHJ.