Home Blog What Size Solar Breaker Can You Back-Feed Into a 400 A Panel With a 200 A Main?

What Size Solar Breaker Can You Back-Feed Into a 400 A Panel With a 200 A Main?

Short answer: 125 A. On a 400 A busbar with a 200 A main, NEC 705.12(B)'s 120% allowance is 480 A, leaving 280 A for the solar breaker — which supports roughly a 24 kW inverter at 240 V.

The rule, applied to this panel

NEC 705.12(B)(3)(2) — the "120% rule" — lets the busbar rating × 1.2 be shared between the main breaker and the sum of back-fed supply breakers, provided the solar breaker sits at the opposite end of the busbar from the main.

Every breaker size on this configuration

Back-fed breakerMain + back-fed120% allowanceHeadroomResult
15 A215 A480 A265 Aallowed
20 A220 A480 A260 Aallowed
25 A225 A480 A255 Aallowed
30 A230 A480 A250 Aallowed
35 A235 A480 A245 Aallowed
40 A240 A480 A240 Aallowed
45 A245 A480 A235 Aallowed
50 A250 A480 A230 Aallowed
60 A260 A480 A220 Aallowed
70 A270 A480 A210 Aallowed
80 A280 A480 A200 Aallowed
90 A290 A480 A190 Aallowed
100 A300 A480 A180 Aallowed
125 A325 A480 A155 Aallowed

Before you rely on this

Passing the arithmetic is necessary but not sufficient. The solar breaker must be at the opposite end of the busbar from the main — that physical placement is what the 120% allowance is premised on, because it keeps the busbar from carrying both sources across its full length. The panel also needs the 705.12(B)(3) warning stating the busbar is fed from multiple sources and the breaker must not be relocated. A reviewer who sees correct arithmetic and no placard will still red-line the set.

If 125 A is not enough for your inverter, the options below apply just as they would to a failing calculation.

Where the 120% rule does not get you there, these are the code-compliant routes:

Related

Checking a real interconnection? OneLine Studio runs this exact calculation live while you draw — and every other one the plan reviewer will check — then prints it into a 10-sheet permit set with the manufacturer datasheets already attached. Describe your system in a sentence and the first one is free: open the studio.

Computed with OneLine Studio's NEC engine — the same deterministic code tables that size a real permit set, not an estimate. Conductor ampacity from NEC 310.16, correction factors from 310.15(B)(1), fill adjustment from 310.15(C)(1). Always confirm the enforced NEC edition and any local amendments with your AHJ.

FAQ

What is the largest solar breaker I can back-feed into a 400 A panel with a 200 A main?

125 A. The 120% allowance is 480 A, the main uses 200 A, leaving 280 A — so 125 A is the largest standard breaker that fits.

What size inverter does that support?

Roughly 24 kW at 240 V single phase. A back-fed breaker must be at least 125% of the inverter's continuous output current, so a 125 A breaker supports about 100 A of continuous output.

Why does the breaker have to be at the opposite end of the busbar?

The 120% allowance assumes the two sources feed from opposite ends, so no single section of busbar carries the full combined current. Relocating the breaker defeats that assumption, which is exactly why 705.12(B)(3) requires a permanent label warning against it.

Educational reference, reviewed 2026-07. A design aid, not a substitute for a licensed electrician or PE. Confirm the enforced NEC edition and local amendments with your AHJ.