ONELINE STUDIO
Home Blog What Size Solar Breaker Can You Back-Feed Into a 200 A Panel With a 100 A Main?

What Size Solar Breaker Can You Back-Feed Into a 200 A Panel With a 100 A Main?

Short answer: 125 A. On a 200 A busbar with a 100 A main, NEC 705.12(B)'s 120% allowance is 240 A, leaving 140 A for the solar breaker — which supports roughly a 24 kW inverter at 240 V.

The rule, applied to this panel

NEC 705.12(B)(3)(2) — the "120% rule" — lets the busbar rating × 1.2 be shared between the main breaker and the sum of back-fed supply breakers, provided the solar breaker sits at the opposite end of the busbar from the main.

Every breaker size on this configuration

Back-fed breakerMain + back-fed120% allowanceHeadroomResult
15 A115 A240 A125 Aallowed
20 A120 A240 A120 Aallowed
25 A125 A240 A115 Aallowed
30 A130 A240 A110 Aallowed
35 A135 A240 A105 Aallowed
40 A140 A240 A100 Aallowed
45 A145 A240 A95 Aallowed
50 A150 A240 A90 Aallowed
60 A160 A240 A80 Aallowed
70 A170 A240 A70 Aallowed
80 A180 A240 A60 Aallowed
90 A190 A240 A50 Aallowed
100 A200 A240 A40 Aallowed
125 A225 A240 A15 Aallowed

Before you rely on this

Passing the arithmetic is necessary but not sufficient. The solar breaker must be at the opposite end of the busbar from the main — that physical placement is what the 120% allowance is premised on, because it keeps the busbar from carrying both sources across its full length. The panel also needs the 705.12(B)(3) warning stating the busbar is fed from multiple sources and the breaker must not be relocated. A reviewer who sees correct arithmetic and no placard will still red-line the set.

If 125 A is not enough for your inverter, the options below apply just as they would to a failing calculation.

Where the 120% rule does not get you there, these are the code-compliant routes:

Related

Checking a real interconnection? OneLine Studio runs this exact calculation live while you draw — and every other one the plan reviewer will check — then prints it into a 10-sheet permit set with the manufacturer datasheets already attached. Describe your system in a sentence and the first one is free: open the studio.

Computed with OneLine Studio's NEC engine — the same deterministic code tables that size a real permit set, not an estimate. Conductor ampacity from NEC 310.16, correction factors from 310.15(B)(1), fill adjustment from 310.15(C)(1). Always confirm the enforced NEC edition and any local amendments with your AHJ.

FAQ

What is the largest solar breaker I can back-feed into a 200 A panel with a 100 A main?

125 A. The 120% allowance is 240 A, the main uses 100 A, leaving 140 A — so 125 A is the largest standard breaker that fits.

What size inverter does that support?

Roughly 24 kW at 240 V single phase. A back-fed breaker must be at least 125% of the inverter's continuous output current, so a 125 A breaker supports about 100 A of continuous output.

Why does the breaker have to be at the opposite end of the busbar?

The 120% allowance assumes the two sources feed from opposite ends, so no single section of busbar carries the full combined current. Relocating the breaker defeats that assumption, which is exactly why 705.12(B)(3) requires a permanent label warning against it.

Educational reference, reviewed 2026-07. A design aid, not a substitute for a licensed electrician or PE. Confirm the enforced NEC edition and local amendments with your AHJ.

Draft this design in minutes — free

Describe a residential solar + storage system in plain English. OneLine Studio drafts the one-line diagram, sizes the conductors, runs these NEC checks live, and builds a permit-ready package.

Start free →