ONELINE STUDIO
Home Blog What Breaker and Wire for a 5 kW Inverter at 113 °F With 9 Conductors?

What Breaker and Wire for a 5 kW Inverter at 113 °F With 9 Conductors?

Short answer: a 30 A breaker, 8 AWG copper conductors and a 10 AWG equipment grounding conductor. A 5 kW inverter puts out 20.8 A continuous at 240 V, and continuous duty means everything is sized at 125% of that — 26 A.

Sizing the overcurrent device

The inverter nameplate is the authority on continuous output current. Where the nameplate differs from 20.8 A — and it often does, because kW ratings are rounded — size from the nameplate, not from the marketing number.

Every conductor, at 113 °F with 9 in the raceway

Temperature correction 0.87 × fill adjustment 0.7 — the conductor has to carry 26 A after both.

Conductor90 °C baseAfter deratingTerminal (75 °C)Result
12 AWG30 A18.3 A25 Ano
10 AWG40 A24.4 A35 Ano
8 AWG55 A33.5 A50 Apasses
6 AWG75 A45.7 A65 Apasses
4 AWG95 A57.9 A85 Apasses
3 AWG110 A67 A100 Apasses
2 AWG130 A79.2 A115 Apasses
1 AWG150 A91.4 A130 Apasses
1/0170 A103.5 A150 Apasses

8 AWG clears with 7.5 A to spare, so there is room if the conditions turn out slightly worse than assumed.

The 110.14(C) trap

The conductor also has to satisfy its terminal rating, which is almost always the 75 °C column even when the wire itself is rated 90 °C. You derate from the 90 °C ampacity, but you compare against the 75 °C terminal — using the 90 °C column at the breaker lug is one of the most common sizing errors, and it fails inspection rather than failing safely.

Related

Sizing a real inverter circuit? OneLine Studio runs this exact calculation live while you draw — and every other one the plan reviewer will check — then prints it into a 10-sheet permit set with the manufacturer datasheets already attached. Describe your system in a sentence and the first one is free: open the studio.

Computed with OneLine Studio's NEC engine — the same deterministic code tables that size a real permit set, not an estimate. Conductor ampacity from NEC 310.16, correction factors from 310.15(B)(1), fill adjustment from 310.15(C)(1). Always confirm the enforced NEC edition and any local amendments with your AHJ.

FAQ

What size breaker for a 5 kW inverter?

30 A at 240 V. The inverter's 20.8 A continuous output is multiplied by 125% per the continuous-duty rule, giving 26 A, rounded up to the next standard size in 240.6(A). Always confirm against the nameplate continuous output current.

What wire size for a 5 kW inverter at 113 °F?

8 AWG copper with 9 current-carrying conductors in the raceway. After a 0.87 temperature correction and a 0.7 fill adjustment it delivers 33.5 A against the 26 A required.

What size EGC?

10 AWG copper, from Table 250.122 for a 30 A overcurrent device. If you upsize the ungrounded conductors for voltage drop, 250.122(B) requires the EGC to be increased proportionally too.

Educational reference, reviewed 2026-07. A design aid, not a substitute for a licensed electrician or PE. Confirm the enforced NEC edition and local amendments with your AHJ.

Draft this design in minutes — free

Describe a residential solar + storage system in plain English. OneLine Studio drafts the one-line diagram, sizes the conductors, runs these NEC checks live, and builds a permit-ready package.

Start free →