ONELINE STUDIO
Home Blog How to size a solar battery for backup

How to size a solar battery for backup

A backup battery is sized by two separate questions: how much energy you need over time (kWh) and how much power you need at once (kW). Get both right and the system carries your home through an outage; get either wrong and it either dies early or trips on startup. Here is the method.

Step 1 — Pick your critical loads

Backup rarely means running the whole house. List the circuits that must stay on during an outage:

Leave out large resistive and high-draw loads — electric ranges, dryers, and central AC — unless you deliberately plan for them, because they dominate both energy and power.

Step 2 — Estimate daily energy (kWh)

For each critical load, multiply its wattage by the hours per day it actually runs, then sum:

Add everything up. A modest critical-loads panel commonly lands around 8 to 12 kWh per day. Use your utility bill as a sanity check on whole-home usage.

Step 3 — Choose days of autonomy

Days of autonomy is how long the battery alone carries the critical loads with little or no solar input:

Multiply daily energy by days of autonomy. At 10 kWh/day and one day, you need 10 kWh delivered.

Step 4 — Adjust for usable depth of discharge

Batteries should not be fully drained. Divide the energy you need by the usable depth of discharge (often 80 to 95% for lithium):

Round up to the next real product size. Round-trip efficiency losses (roughly 90%) further nudge you toward a slightly larger pack.

Step 5 — Check the power rating (kW)

Now confirm the battery inverter can supply the simultaneous draw. Add the running watts of loads that overlap, and account for motor surge on pumps, compressors, and the furnace blower, which can spike to several times running current at startup. If the continuous kW rating is too low, the system trips even when plenty of kWh remain.

Design inputWhat it sets
Critical load kWh/dayBattery energy capacity
Days of autonomyMultiplier on capacity
Continuous kW ratingHow many loads run at once
Surge kW ratingWhether motors start cleanly

A quick worked example

Say your critical loads total 9 kWh/day, you want one day of autonomy, your battery has 90% usable depth of discharge, and your largest simultaneous draw (fridge plus furnace blower plus lights, with motor surge) peaks around 4 kW:

If you later want two days of autonomy, the energy figure simply doubles to about 20 kWh while the power rating stays the same.

Hook: grade your solar design free - same NEC checks a reviewer runs.

Battery interconnection also touches the 120% busbar rule and, depending on chemistry, DC- or AC-coupled wiring — plan those early with our reference library. Confirm requirements with your AHJ, and have a licensed electrician or PE review and stamp the installation. For array sizing, see how to size a residential solar system.

FAQ

How many kWh of battery do I need for backup?

Multiply your critical daily load in kWh by your desired days of autonomy, then divide by the battery's usable depth of discharge to get the nameplate capacity.

What is depth of discharge?

The share of a battery's rated capacity you can safely use; a 10 kWh battery at 90% usable depth of discharge delivers about 9 kWh before it should recharge.

Does battery size limit how much I can run at once?

Capacity in kWh sets how long you run; the battery inverter's continuous power rating in kW sets how many appliances you can run at the same instant.

Related: Design & sizing

Educational reference, reviewed 2026-07. A design aid, not a substitute for a licensed electrician or PE. Confirm the enforced NEC edition and local amendments with your AHJ.

Draft this design in minutes — free

Describe a residential solar + storage system in plain English. OneLine Studio drafts the one-line diagram, sizes the conductors, runs these NEC checks live, and builds a permit-ready package.

Start free →