ONELINE STUDIO
Home Blog Conductor ampacity derating — temperature and conduit fill

Conductor ampacity derating — temperature and conduit fill

A PV conductor has to pass more than one ampacity test, and beginners often stop after the first. Between the wire's table rating and the current it actually carries sit two derates and one termination cap. Skip any of them and you get either an overheated conductor or a plan-review correction.

Start with the table rating

Every conductor has a base ampacity from NEC Table 310.16 at a given insulation temperature rating — 60 C, 75 C, or 90 C. PV wire and THWN-2 are commonly 90 C rated, which is useful because derating is applied against the 90 C column, giving you headroom before the final termination check. See the wire ampacity table.

Derate 1: ambient temperature

Ampacity tables assume a 30 C ambient. Where it's hotter, multiply by the temperature-correction factor from Table 310.15(B). Two twists matter for solar:

Derate 2: conduit fill

When more than three current-carrying conductors share a raceway, apply the conduit-fill adjustment factor (for example, 80% for 4-6 conductors). Count carefully — on the DC side, series strings and the way you count conductors affect this.

The two derates multiply together against the 90 C ampacity:

StepBasisEffect
Table rating310.16, 90 C columnStarting ampacity
Ambient + rooftop310.15(B) factorMultiply (< 1)
Conduit fill310.15(C) factorMultiply (< 1)
Derated ampacityProduct of aboveMust exceed circuit current

The termination check: 110.14(C)

Here's the catch that trips everyone. Even after you derate from the 90 C column, 110.14(C) caps the usable ampacity at the temperature rating of the terminals the conductor lands on — commonly 75 C for breakers and lugs. So you run two parallel calculations:

1. Derated ampacity from the 90 C column (both derates applied) must exceed the circuit's continuous current. 2. Terminal check: the conductor's 75 C column ampacity (no derates) must meet the required load per the terminal rating.

The conductor must satisfy both. The 90 C rating buys derating headroom; the 75 C terminal rating sets the connection ceiling.

A quick worked feel

Say a THWN-2 conductor lists 40 A at 90 C. On a hot roof the ambient-plus-rooftop correction might be 0.82, and sharing a raceway with five other current-carrying conductors adds a 0.80 fill factor. Multiply: 40 x 0.82 x 0.80 = about 26 A of usable derated ampacity. That single conductor went from a comfortable 40 A on paper to 26 A in the real installation — and if the circuit's continuous current is 24 A, you're close enough that the next hotter day or an added conductor pushes you over. This is why derating is never optional.

How it fits the bigger picture

This derating is one of three ampacity checks a PV conductor must clear: the 690.8 minimum current, this environmental derate, and the 110.14 termination. See how it fits the full design in how to size a residential solar system. The checks compete — sometimes the derate governs, sometimes the terminal cap does — so you run all of them and take the largest conductor. Miss the rooftop adder and a summer inspection can find undersized DC conductors that were "fine" on the spreadsheet.

Want your conductor sizing sanity-checked? Grade your solar design free - we run the same NEC checks a plan reviewer would.

Correction factors and rooftop adders shifted between NEC editions; confirm the enforced code and local amendments with your AHJ, and have a licensed electrician or PE review, sign and stamp the design before filing or energizing.

FAQ

What are the two derating factors for conductor ampacity?

Ambient-temperature correction (from the conductor temperature-rating column of Table 310.15(B)) and conduit-fill adjustment for more than three current-carrying conductors in a raceway.

What is the 110.14(C) termination check?

110.14(C) limits the usable ampacity to the terminal's temperature rating — often 75 C — so even a 90 C conductor's rating is capped at the 75 C column value where it lands on the equipment.

Do rooftop conduits need extra temperature correction?

Yes — conduit exposed to sunlight on a rooftop runs hotter than ambient, so add the rooftop temperature adder before selecting the ambient-correction factor.

Related: NEC code explained

Educational reference, reviewed 2026-07. A design aid, not a substitute for a licensed electrician or PE. Confirm the enforced NEC edition and local amendments with your AHJ.

Draft this design in minutes — free

Describe a residential solar + storage system in plain English. OneLine Studio drafts the one-line diagram, sizes the conductors, runs these NEC checks live, and builds a permit-ready package.

Start free →